Global Journal of Technology and Optimization

Manuskript einreichen arrow_forward arrow_forward ..

SIZING OF A PV/H2 HYBRID SYSTEM TO SUPPLY PEAK LOADS ON AN ISOLATED ELECTRICAL GRID – A CASE STUDY IN CORSICA ISLAND (FRANCE)

Abstract

C Cristofari, JI Canaletti, C Darras, M Muselli

The object of the study is to reduce the daily load peaks on an insular electric network (Corsica Island, France) using with help to renewable energy systems. The methodology is based on an energy balance between a PV array, an electrolyzer and fuel cells (50 kW) supplying a seasonal load profile built from electrical network load peaks. This load is supplied firstly by the PV array and the fuel cell produces complementary power when the PV system is deficient. An electrolyzer, using unconsumed PV energy produces hydrogen for the fuel cell. In the present work, at the beginning of the operation, the hydrogen stock is sufficient to satisfy a given number of days corresponding to the system autonomy (Loss of Load probability = 0). Solar and ambient temperature data were measured at our laboratory weather station in Ajaccio (41°55' N, 8°48' E, 70 m altitude). Hourly data are available for the years 1998 to 2004. The originality of this approach was to determine a whole methodology allowing obtaining quickly sizing curves for a PV/H2 hybrid system supplying a given load (remote sites and/or grid connection).

Haftungsausschluss: Dieser Abstract wurde mit Hilfe von Künstlicher Intelligenz übersetzt und wurde noch nicht überprüft oder verifiziert

Teile diesen Artikel

arrow_upward arrow_upward